S7TIA symbolic address harmonizing doesn't work if there are groupings in the TIA Project

S7TIA symbolic address harmonizing doesn't work if there are groupings in the TIA Project

Summary

The address harmonizing which means, the different Interpretation when the driver is set to read the symbol information direct from the online PLC, but the variables are browsed offline from the TIA Project, is not considering groubs and subgroups of blocks. When browsing offline, groups should be marked with two points as separator [..] to clearly identfy the group for correct address harmonizing.

Description

The address harmonizing which means, the different Interpretation when the driver is set to read the symbol information direct from the online PLC, but the variables are browsed offline from the TIA Project, is not considering groubs and subgroups of blocks. When browsing offline, groups should be marked with two points as separator [..] to clearly identfy the group for correct address harmonizing.

Information

It is always possible to keep the option "Symbols from Tia Project" active



Issue Number: 206131
Fixed on Date: 29.1.2020
Versions: 7.60 0 BUILD 63571 | 8.10 0 BUILD 63771 | 7.60 0 BUILD 64404 | 8.00 0 BUILD 64633 | 7.50 0 BUILD 64982 | 7.20 0 BUILD 66073