Under specific circumstances with a 7.11 runtime server / standby server or a 7.20 runtime server / standby server and a 7.50 runtime client, the runtime on the server may close unexpectedly after the client opens a batch control screen or a command sequencer screen, when the server performed a redundancy switch earlier.
Under specific circumstances with a 7.11 runtime server / standby server or a 7.20 runtime server / standby server and a 7.50 runtime client, the runtime on the server may close unexpectedly after the client opens a batch control screen or a command sequencer screen, when the server performed a redundancy switch earlier.
An issue has been addressed in the runtime where under specific circumstances the runtime may close unexpectedly on the current primary server, after a client opened a batch control screen or a command sequencer screen.
available in 7.11 from build 21784