On the Smart Client,
a reaction matrix that is linked to a local variable is not triggered in
zenon 12. This is independent of whether the reaction matrix is linked to an
internal driver variable that is set to calculate "locally" or
to a SYSDRV variable like "computer name". In version 11,
triggering the reaction matrix works.
Cause:
Due to a serialization issue, the configured reactionmatrices could not be read and therefor where not triggered. If a limit value was present, it was used as fallback.
This error has been fixed. Reaction matrices are triggered in the Smart Client in zenon12 again as expected.
To benefit from this fix: