Rated redundancy does not correctly consider internal variables set to calculation "Network" in the rating matrix
Summary
When internal driver variables with calculation "Network" are used in the rated redundancy matrix with the option to validate the value / status, the rating does not consider these values invalid after a redundancy switch.
Description
When internal driver variables with calculation "Network" are used in the rated redundancy matrix with the option to validate the value / status, the rating does not consider these values invalid after a redundancy switch.
Solution
An issue has been addressed in the evaluation of internal driver variables with the calculation set to "Network".
Issue Number: 30678
Fixed on Date: 15.1.2016
Versions: 7.50 0 BUILD 25796