Print current values -> exception code 0xc0000409 STATUS_STACK_BUFFER_OVERRUN

Print current values -> exception code 0xc0000409 STATUS_STACK_BUFFER_OVERRUN

Description

When printing current values in the Service Engine, zenon is terminated without an error message. Windows logs an error "0xc0000409 STATUS_STACK_BUFFER_OVERRUN". The print job refers to an internal driver string variable that has a long initial value. This error does not occur with a very short value.

This error has been fixed. Printing now also works as expected with long values.

To benefit from this fix:

  • Update your zenon Software Platform to the latest build of zenon 8.20 or higher.

 



Item ID: 269930
Version: 12.00 Build: 179985
Version: 12.00 Build: 180966
Version: 11.00 Build: 176384
Version: 10.00 Build: 176923
Version: 8.20 Build: 174392