PGW AccessIEC870Slave in 101 balanced, after TF1.2 ack (e.g. E5 char) looses next ASDU if it is already in the reception buffer
Description
The zenon Process Gateway
AccessIEC870Sl as an
IEC 60870-5-101 slave with balanced transmission discarded the serial receive buffer when processing confirmation frames (or single character control). If there were already other frame characters in the buffer, they could not be processed. For example, this could result in an execute command not being executed.
The issue has been addressed and the buffer is no longer discarded.
To benefit from this fix:
- Update your zenon Software Platform to the latest build of zenon 12 or higher.
Item ID: 302756
Version: 15.00 Build: 440528
Version: 14.00 Build: 435445
Version: 12.00 Build: 436099