OPCUA32: static variables remain INVALID after very short connection loss

OPCUA32: static variables remain INVALID after very short connection loss

Summary

When the OPCUA32 OPC UA client driver experiences a short connection loss, and the connection can be re-established immediately, variables that do not change on the OPC UA server side, remain with INVALID status in the runtime, until the value changes on OPC UA server side.

Description

When the OPCUA32 OPC UA client driver experiences a short connection loss, and the connection can be re-established immediately, variables that do not change on the OPC UA server side, remain with INVALID status in the runtime, until the value changes on OPC UA server side.



Issue Number: 105654
Fixed on Date: 6.11.2019
Versions: 8.00 0 BUILD 62073 | 8.10 0 BUILD 61858 | 7.50 0 BUILD 61995 | 7.60 0 BUILD 63571