Omron Hostlink driver (OMRON32) the driver doesn't convert BCD values for UDINT variables when the value is bigger then 9999

Omron Hostlink driver (OMRON32) the driver doesn't convert BCD values for UDINT variables when the value is bigger then 9999

Summary

The variable is configured with the driver object type DM-Area BCD and the data type is UDINT.

The value is right until 9999 but then the automaticaly convertion doesn't work and for example the value 10000 is then visualized as 65536.

Description

The variable is configured with the driver object type DM-Area BCD and the data type is UDINT.

The value is right until 9999 but then the automaticaly convertion doesn't work and for example the value 10000 is then visualized as 65536.

Solution

Redesigned the conversion. The BCD DWORDs will be read and is written correctly.



Issue Number: 33137
Fixed on Date: 16.12.2014
Versions: 7.00 0 BUILD 25 | 7.11 0 BUILD 17075