MODBUS_ENERGY: multiple stations with different Modbus Unit ID and one IP address: driver crashes in the runtime when the driver is stopped

MODBUS_ENERGY: multiple stations with different Modbus Unit ID and one IP address: driver crashes in the runtime when the driver is stopped

Summary

MODBUS_ENERGY driver - Issue when the option join connections is active. If the MODBUS gateway is disconnected and connections to this gateway exist which have not yet been activated (no variable of the connection has been requested since runtime start) the driver stops working.

Description

MODBUS_ENERGY driver - Issue when the option join connections is active. If the MODBUS gateway is disconnected and connections to this gateway exist which have not yet been activated (no variable of the connection has been requested since runtime start) the driver stops working.

Information

delet the variables with this driver



Issue Number: 171694
Fixed on Date: 9.1.2019
Versions: 8.00 0 BUILD 55271 | 7.60 0 BUILD 56016 | 8.10 0 BUILD 57250 | 8.20 0 BUILD 65124
    • Related Articles

    • MODBUS ENERGY: Support for RTU frames over TCP/IP

      Summary The Modbus Energy driver supports communication of RTU frame via TCP/IP. Description For this purpose, the new Modbus TCP/RTU frame via TCP radio button has been implemented in the Settings tab of the driver configuration dialog. Item ID: ...
    • Modbus_Energy driver: Status of TCP/IP connection is not displayed

      Description For variables from the Modbus Energy driver, the status of the TCP/IP connection is not displayed in the Service Engine for suitable elements. This behavior has been changed. The connection status is now displayed. To benefit from this ...
    • Checklist: Communication to TwinCat via BeckhoffNG driver

      Time estimate: 30 minutes Please go through all the points in the following checklist. If necessary, confirm with IT Department any information you cannot verify before contacting your local COPA-DATA Representative. TwinCAT ADS communication library ...
    • Data points with the same COA/IOA address but different Typ-ID are overwritten.

      Summary Values for variables with the same COA/IOA address but different and not compatible Type ID are overwritten by IEC870 driver. This behavior has been changed. Description In non-standard conforming RTUs there can be 2 IOs with the same COA/IOA ...
    • Checklist: Driver(s) cannot establish a reliable communication

      Time estimate: 60 minutes Please go through all the points in the following checklist. If necessary, confirm with IT Department any information you cannot verify before contacting your local COPA-DATA Representative. Checklist usage: #. [Quick hints] ...