MELSECA: When primary server comes back online (dominant) the MELSECA driver on the standby server is not stopped (keeps the TCP connection alive) and the MELSECA driver on primary can no longer connect to the PLC and therefore the variable gets invalid
Summary
TCP Connections are not closed on Driver stop
Description
TCP Connections are not closed on Driver stop
Issue Number: 221250
Fixed on Date: 8.7.2020
Versions: 8.10 0 BUILD 67223 | 8.20 0 BUILD 67231
Related Articles
FAQ: Initialization of Internal variables (Network) in Dominant redundancy mode.
When (re-)starting the dominant Server 1, regardless of their 'Remanence' configuration, internal variables with calculation in 'Network' are initialized first in the dominant Server 1 and only after synchronized with the running Server 2. Modules ...
Checklist: Client/Standby cannot establish a reliable connection with Service Engine Server
Time estimate: 45 minutes Please go through all the points in the following checklist. If necessary, confirm with IT Department any information you cannot verify before contacting your local COPA-DATA Representative. Checklist usage: #. [Quick hints] ...
Checklist: Driver(s) cannot establish a reliable communication
Time estimate: 60 minutes Please go through all the points in the following checklist. If necessary, confirm with IT Department any information you cannot verify before contacting your local COPA-DATA Representative. Checklist usage: #. [Quick hints] ...
zenon Changesets Excel
Here, you can access a comprehensive list of changes across all maintained versions of the zenon Software Platform as Excel Worksheets. This includes both implemented bug-fixes and new features. Additionally, these lists are available in CSV format ...
zenon Changesets CSV
Here, you can access a comprehensive list of changes across all maintained versions of the zenon Software Platform as Excel Worksheets. This includes both implemented bug-fixes and new features. Additionally, these lists are available in as Excel ...