When executing a Recipegroup Manager function with the option to read the graphic recipe variables, the local system driver variables that indicate for which recipegroup, recipe, recipe version etc. the action has been called, are updated on all PCs in the network like the global system driver variables, instead of just on the local PC where the function is actually executed.
When executing a Recipegroup Manager function with the option to read the graphic recipe variables, the local system driver variables that indicate for which recipegroup, recipe, recipe version etc. the action has been called, are updated on all PCs in the network like the global system driver variables, instead of just on the local PC where the function is actually executed.
An issue has been addressed in the runtime with the updating of the system driver variables for the Recipegroup Manager. Now the local system driver variables are only updated on the local machine where the action is executed.