linear value adjustment confgured at the variable is not correctly considered in RGM
Summary
When a linear value adjustment is configured at a variable, this is not correctly considered in all circumstances in the Recipe Groups Manager. At reading and writing shadow variables and recipes, the adjusted range is not considered, and a "value out of range" occurs, which is represented via the system driver variable for the status of read recipe / write recipe.
Description
When a linear value adjustment is configured at a variable, this is not correctly considered in all circumstances in the Recipe Groups Manager. At reading and writing shadow variables and recipes, the adjusted range is not considered, and a "value out of range" occurs, which is represented via the system driver variable for the status of read recipe / write recipe.
Solution
An issue has been addressed in the Recipe Groups Manager module where the linear value adjustment was not considered correctly. Now the linear value adjustment is considered and the correct value is read / written.
Information
available from 7.00 SP0 build 6
Issue Number: 28623
Fixed on Date: 16.1.2013
Versions: 7.00 0 BUILD 6
Related Articles
XML export of a standard recipe exports the wrong value when linear value adjustment is used
Summary When a variable used in a standard recipe uses linear value adjustment, e.g. PLC value 0-255 and zenon value 0-2.55, a value "1" in the recipe is incorrectly saved as a value "0.01" in the XML file when the recipe is XML exported. Description ...
Allocation target variables do not correctly consider non-linear value adjustment
Summary A target variable used at an allocation that has macros linked for non-linear value adjustment, doesnot call the AdjustScadaValue macro prior to writing the value if the source variable at the allocation changes the allocation is triggered ...
The value of the recipe variable in the runtime is not displayed correctly in a keyboard screen when linear value adjustment is used
Summary When editing a recipe variable from the recipe value table in the Recipegroup manager screen in the runtime using a configured keyboard screen, the current value is not displayed correctly when the variable uses linear value adjustment. ...
FAQ: It seems that sometimes not all variables are correctly written to the PLC by the RGM module, although the system driver variable states that the recipe was written successfully and the option "write synchronously" is active. How can this be?
When reading a RGM recipe immediately after writing a RGM recipe, with a driver that has the option "keep update list in memory" active, and recipe variables that have been read previously, it can happen that a read cycle is currently in progress, ...
Set value uses wrong range for variable with linear range adjustment using the element input field of the dynamic text
Description When writing the set value for a variable with a linear range adjustment via a text field, the signal range is offered instead of the configured value range. When the set value is entered via the set value dialog or a numeric value ...