In Watchdog timer 'none' and SBO the command action resets PROGRESS bit first when COT_actterm (10) comes or action timeout is elapsed.
Summary
Command Processing by Watchdog timer 'none' sets the PROGRESS status bit of response variable (RV) after Select confirmation and keeps until PLC responds with Execute activation termination - COT_actterm (10).
The PROGRESS bit should gone already when Execute confirmation, not termination, comes - COT_actcon (7), like it is by Watchdog timer 'only RV'.
Description
Command Processing by Watchdog timer 'none' sets the PROGRESS status bit of response variable (RV) after Select confirmation and keeps until PLC responds with Execute activation termination - COT_actterm (10).
The PROGRESS bit should gone already when Execute confirmation, not termination, comes - COT_actcon (7), like it is by Watchdog timer 'only RV'.
Solution
Now, the command action - by watchdog timer 'none' and SBO active - resets the status bit PROGRESS when COT_actcon is received.
Issue Number: 30052
Fixed on Date: 11.12.2013
Versions: 7.20 0 BUILD 17768