During the redundancy switch between primary and secondary IP in IEC60870 driver (Master) - according procedure introduced by Edition 2 of the IEC60870-5-104 Standard - the slave can still send some frames. But when the procedure starts - with APCI frame 'StopDT act' - the driver neither acknowledges to the slave the received data frames nor transfers data to the zenon Runtime.
During the redundancy switch between primary and secondary IP in IEC60870 driver (Master) - according procedure introduced by Edition 2 of the IEC60870-5-104 Standard - the slave can still send some frames. But when the procedure starts - with APCI frame 'StopDT act' - the driver neither acknowledges to the slave the received data frames nor transfers data to the zenon Runtime.
Now the driver processes received data even during it waits for StopDT confirmation and then checks if all pending data has been acknowledged.