IEC61850 Server refuses connection from Relab software client

IEC61850 Server refuses connection from Relab software client

Summary

The IEC61850 Client from Relab software cannot connect to straton/zenon Logic driver IEC61850 Server.

Description

The IEC61850 Client from Relab software cannot connect to straton/zenon Logic driver IEC61850 Server.

Solution

The driver now supports in OSI presentation layer the item protocol-version for MMS.

Information

Fixed on 25.04.2012 in version 6000 of T5BusIec850s.dll; available from 7.00 SP0 Build 1; available from 6.51 SP0 Build 14.



Issue Number: 26748
Fixed on Date: 25.4.2012
Versions: 7.00 0 BUILD 1 | 6.51 0 BUILD 14