IEC61850 Server driver has wrong reaction on MMS.Read request with the flag "SpecificationWithResult" set to TRUE

IEC61850 Server driver has wrong reaction on MMS.Read request with the flag "SpecificationWithResult" set to TRUE

Summary

The support of the flag "SpecificationWithResult" in MMS.Read is theoretical mandatory but seldom in use - thus not requested by clients. Issue found during tests for certification:

The IEC61850 Server supports it only if the read request did include only one variable. For multiple variables the response on the read request is then malformed.

Description

The support of the flag "SpecificationWithResult" in MMS.Read is theoretical mandatory but seldom in use - thus not requested by clients. Issue found during tests for certification:

The IEC61850 Server supports it only if the read request did include only one variable. For multiple variables the response on the read request is then malformed.

Solution

Issue was addressed in putting VariableAccessSpecification to data stream.



Issue Number: 32001
Fixed on Date: 22.5.2014
Versions: 7.10 0 BUILD 13311