In straton/zenon Logic driver IEC61850 Server when a reported Data Object contains an array attribute, the value change of an array element does not trigger any Report.
In straton/zenon Logic driver IEC61850 Server when a reported Data Object contains an array attribute, the value change of an array element does not trigger any Report.
Now the driver handles TrgOps=dchg of data attributes being the array elements too.
Fixed on 28.03.2012 in version 5900 of T5BusIec850s.dll; available from 7.00 SP0 Build 1; available from 6.51 SP0 Build 14.