IEC61850 Server: data inconsistency in reports when timestamp is from variable for t-attribute

IEC61850 Server: data inconsistency in reports when timestamp is from variable for t-attribute

Summary

When t-attribute of a data object is managed manually in the zenon Logic project, a report may have been generated with the previous timestamp of the value change.

Description

When t-attribute of a data object is managed manually in the zenon Logic project, a report may have been generated with the previous timestamp of the value change.

Information

No workaround.

Theoretically, would be possible to write program in logic which in separated cycles, first maps t-attribute from the timestamp of zenon variable, and in next cycle - its status bits and value. Maybe tolerable to do on few variables, but not on many. And there is then still risk of data inconsistency: that updated t-attribute would be sent in the report about data change in other DO, and the relevant value/quality change for this DO - in the next report.



Issue Number: 219063
Fixed on Date: 17.6.2020
Versions: 8.10 0 BUILD 66840 | 8.20 0 BUILD 66627