IEC61850 Client drivers – zenon and Logic – are processing consistency scans (acquisition of missing Quality) in Logical Device of RCB, not of Data Object.
Summary
Issue in iec850 driver in zenon and IEC61850 Client driver in zenon Logic:
when a Data Set used in Report Control Block (RCB):
- contains single Data Attributes (FCDA with daName)
- and the FCDA is placed in different Logical Device as RCB
- and the IED does not deliver Quality (q-attribute) in reports
then the driver processes data consistency scans (polling of missing q-attributes) referring wrong Logical Device. It refers LD of RCB, not of FCDA.
As result the driver may behave unstable.
Description
Issue in iec850 driver in zenon and IEC61850 Client driver in zenon Logic:
when a Data Set used in Report Control Block (RCB):
- contains single Data Attributes (FCDA with daName)
- and the FCDA is placed in different Logical Device as RCB
- and the IED does not deliver Quality (q-attribute) in reports
then the driver processes data consistency scans (polling of missing q-attributes) referring wrong Logical Device. It refers LD of RCB, not of FCDA.
As result the driver may behave unstable.
Solution
The client now scans missing data attribute q from the correct device.
Information
In zenon Logic - IEC61850 Client - the period of scan is fix – 5 minutes.
In iec850 zenon driver this is a setting.
Issue Number: 36828
Fixed on Date: 25.7.2016
Versions: 7.50 0 BUILD 30617
Related Articles
Checklist: Data Missing in Service Engine
Time estimate: 60 minutes Please go through all the points in the following checklist. If necessary, confirm with IT Department any information you cannot verify before contacting your local COPA-DATA Representative. Checklist usage: #. [Quick hints] ...
FAQ: Where can I find the XML device profile for COPA-DATA DNP3 drivers?
What is a DNP3 XML device profile? Where can I find the XML device profile for one of the following drivers? DNP3_TG - Subset Level 1,2,3 and 4 for both requests and responses, DNP3 Master driver for zenon Service Engine AccessDNP3_SG - Subset Level ...
zenon logic: Unexpected complex data in expression
In zenon version 8.20, it was possible to initiate and assign the function block in one line. This was not IEC compliant, therefore feature was removed in zenon 10. Now the error message "Unexpected complex data in expression" is logged when using ...
zenon Changesets Excel
Here, you can access a comprehensive list of changes across all maintained versions of the zenon Software Platform as Excel Worksheets. This includes both implemented bug-fixes and new features. Additionally, these lists are available in CSV format ...
zenon Changesets CSV
Here, you can access a comprehensive list of changes across all maintained versions of the zenon Software Platform as Excel Worksheets. This includes both implemented bug-fixes and new features. Additionally, these lists are available in as Excel ...