IEC61850 Client driver ignores configuration setting for dynamic data set

IEC61850 Client driver ignores configuration setting for dynamic data set

Summary

The iec850 driver (zenon and Logic) ignores the configuration settings for dynamic data set and enables RCB with the DataSet as it is currently in RCB, so also with empty name.

There are no entries in Log about try to use/create dynamic data set (only about deleting of the superfluous data sets and enabling of RCB like by RCBs with static data sets).

Description

The iec850 driver (zenon and Logic) ignores the configuration settings for dynamic data set and enables RCB with the DataSet as it is currently in RCB, so also with empty name.

There are no entries in Log about try to use/create dynamic data set (only about deleting of the superfluous data sets and enabling of RCB like by RCBs with static data sets).

Solution

Now the dataset name is extracted correctly.

Information

Issue reproducible in zenon 7.10 builds up 29.03.2012.



Issue Number: 31176
Fixed on Date: 24.1.2014
Versions: 7.10 0 BUILD 10378