Summary In specific project configuration/offset constellation invalid Bit is set when a FLOAT variable is seen in a screen even if all offset configuration is correct. The problem occurs when in the driver configuration it is enabled the "Offset ...
Here, you can access a comprehensive list of changes across all maintained versions of the zenon Software Platform as Excel Worksheets. This includes both implemented bug-fixes and new features. Additionally, these lists are available in CSV format ...
Summary Issue in zenon Process Gateway IEC 60870 Slave by DPI/DCS mapping when one zenon variable is configured in a sector many times. If you create in a sector two or more IOs as 'double point information' - type id. <3>, <4> or <31> - and link ...
Here, you can access a comprehensive list of changes across all maintained versions of the zenon Software Platform as Excel Worksheets. This includes both implemented bug-fixes and new features. Additionally, these lists are available in as Excel ...
Summary IEC61850 Client driver does not set the T_STD bit at the zenon variables getting external timestamp - from t-attribute (variables with FC= ST or MX, e.g. */stVal[ST]). The driver uses correctly T_STD bit but only by T_INTERN timestamps, not ...