GOOSE Publisher: missing 802.1Q field in GOOSE header when VLAN ID=0
Summary
zenon Logic I/O driver ‘IEC 61850 Server with GOOSE’ as Publisher places 802.1Q field into GOOSE header only when VLAN ID > 0. Even when VID=0 the driver should include the 802.1Q, in order to set the message priority - if priority is different default.
Description
zenon Logic I/O driver ‘IEC 61850 Server with GOOSE’ as Publisher places 802.1Q field into GOOSE header only when VLAN ID > 0. Even when VID=0 the driver should include the 802.1Q, in order to set the message priority - if priority is different default.
Solution
Now the 802.1Q field is included when VLAN ID or priority are <> default.
Information
Note: in Standard defines defaults are: for ID is 0, for priority is 4.
Issue Number: 28813
Fixed on Date: 26.2.2013
Versions: 7.10 0 BUILD 6571