Description The IEC61850 server published GOOSE messages if the test bit was set and LPHD1.Sim.stVal has been set to TRUE. The issue has been addressed and GOOSE messages are no longer published with simulation set, when LPHD*.Sim.stVal is set to ...
Summary It is not possible to correctly modify the Workbench/Runtime Host and Port parameters of a zenon Logic Project in the Editor. After the first modification, it is no longer possible to revert to the original settings. DescriptionIt is not ...
Summary zenon Logic I/O driver ‘IEC 61850 Server with GOOSE’ as Subscriber is not updating timestamp - the value of t-variable – when received in GOOSE message from a Publisher. In earlier builds of 7.10 and versions was OK. Descriptionzenon Logic ...
Summary zenon Logic I/O driver ‘IEC 61850 Server with GOOSE’ as Publisher places 802.1Q field into GOOSE header only when VLAN ID > 0. Even when VID=0 the driver should include the 802.1Q, in order to set the message priority - if priority is ...
Summary The zenon Logic I/O driver IEC61850 Server as GOOSE Subscriber is processing data changes received in GOOSE messages with the flag NdsCom set to TRUE. This flag means that on Publisher the GOOSE Control Block needs commissioning, so ...