GIS Control: Error-prone Storage of Equipment Groups

GIS Control: Error-prone Storage of Equipment Groups

Summary

Information from Equipment Groups  is stored incorrectly in the GIS. This is due to a non-permitted separator in the path. Now only a dot is allowed as a separator.

Description

Errors occur when saving information from Equipment Groups in GIS.

Cause:

In the GIS configuration, the separator # can be used for the path of Equipment Groups. For example: ZENON11_Model#GroupA#SubGroupA".

# is a separator allowed for Equipment Groups. However, it must not be used in GIS. Paths for Equipment Groups with a # are not considered in GIS.

Solution:

The # separator has been forbidden in Equipment Groups. The only allowed separator is now a dot. Project and Equipment Groups are still seperated by #
For example:
ZENON11_DEMO#Plant.Packaging.Line 1.Filler

To benefit from this fix:

  • Upgrade to the latest build of zenon Software Platform 10 or later.
  • Replace any # in paths of Equipment Groups in your GIS configuration with a dot. But remember that # is used as a separator between project and Equipment Groups.



Item ID: 255306
Version: 11.00 Build: 106404
Version: 10.00 Build: 106141