Feedback Variables configured for a recipe group are not set correctly on a runtime client.
Summary
Variables that are linked to a recipe group for group specific status information, do not contain the correct values after recipe actions, when these actions are executed on a client. If the recipe actions are executed on the server or in a standalone runtime the variables linked to the group contain the correct information.
Description
Variables that are linked to a recipe group for group specific status information, do not contain the correct values after recipe actions, when these actions are executed on a client. If the recipe actions are executed on the server or in a standalone runtime the variables linked to the group contain the correct information.
Solution
An issue was addressed in the runtime where the status variables linked to recipe groups were not correctly set when recipe actions were performed on a network client. Now the status information is correctly written to the linked variables, also when the recipe action is performed on a client.
Issue Number: 30192
Fixed on Date: 1.10.2013
Versions: 7.00 0 BUILD 13 | 7.10 0 BUILD 7770
Related Articles
FAQ: When I activate the option "write synchronously" for the Recipegroup manager recipe, and I write the recipe, the recipe does not seem to be written properly and also the Service Engine does not close properly. Why is that?
When the option "write synchronously" is active at a recipe, when writing a recipe (sending values to the PLC) for each recipe variable a writing confirmation is requested to the driver. On a successfull write, the driver sends a writing confirmation ...
Recipe variables in the recipe value table in the Recipegroup Manager screen are not always correctly set invisible
Summary It can happen that Recipegroup Manager recipe variables are still displayed in the recipe value table in the Recipegroup Manager screen in the runtime, although the linked visiblity variable have an active limit with the invisible attribute ...
FAQ: It seems that sometimes not all variables are correctly written to the PLC by the RGM module, although the system driver variable states that the recipe was written successfully and the option "write synchronously" is active. How can this be?
When reading a RGM recipe immediately after writing a RGM recipe, with a driver that has the option "keep update list in memory" active, and recipe variables that have been read previously, it can happen that a read cycle is currently in progress, ...
Drag&Drop of recipe variables from one recipe group to another recipe group in the editor does not work as expected
Summary When attempting to use drag&drop to move or copy recipe variables from one recipe group to another recipe group, the recipe variables may not update correctly and the editor may close unexpectedly. Description When attempting to use drag&drop ...
FAQ: HTML5 WebEngine local variables are mirrored to all clients?
Variables used in the WebEngine are mirrored into all HTML5 Clients. If a HTML5 Client has write access, it can alter variables for the native Service Engine and all connected HTML5 clients even when the calculation of the variable is set to "local". ...