Error message "The data of the Batch module of project '...' were edited with version (7.00 SP0). and cannot be loaded here!" when starting a client / webclient in the version 7.10 with a server running version 7.00
Summary
When starting a client or webclient in version 7.10 with a server runtime running version 7.00, where a license for Batch Control is used, the runtime shows an error message on startup. "The data of the Batch module of project '...' were edited with version (7.00 SP0). and cannot be loaded here!"
The runtime is closed when the error message is acknowledged. In the project itself, the Batch Control module is not used.
Description
When starting a client or webclient in version 7.10 with a server runtime running version 7.00, where a license for Batch Control is used, the runtime shows an error message on startup. "The data of the Batch module of project '...' were edited with version (7.00 SP0). and cannot be loaded here!"
The runtime is closed when the error message is acknowledged. In the project itself, the Batch Control module is not used.
Solution
An issue has been addressed in the compatibility checks for the Batch Control module in the runtime. It is now possible for a 7.10 client to connect to a 7.00 server if there are no batch units in the project, regardless whether a license for Batch Control exists or not.
Issue Number: 31170
Fixed on Date: 23.1.2014
Versions: 7.10 0 BUILD 10378
Related Articles
Checklist: Data Missing in Service Engine
Time estimate: 60 minutes Please go through all the points in the following checklist. If necessary, confirm with IT Department any information you cannot verify before contacting your local COPA-DATA Representative. Checklist usage: #. [Quick hints] ...
Checklist: Client/Standby cannot establish a reliable connection with Service Engine Server
Time estimate: 45 minutes Please go through all the points in the following checklist. If necessary, confirm with IT Department any information you cannot verify before contacting your local COPA-DATA Representative. Checklist usage: #. [Quick hints] ...
Checklist: OPCDA Server
Time estimate: 20 minutes Please go through all the points in the following checklist. If necessary, confirm with IT Department any information you cannot verify before contacting your local COPA-DATA Representative. Do NOT use DCOM in combination ...
Checklist: Workspace/Project cannot be created, loaded or backed up
Time estimate: 30 minutes Please go through all the points in the following checklist. If necessary, confirm with IT Department any information you cannot verify before contacting your local COPA-DATA Representative. Checklist usage: #. [Quick hints] ...
Checklist: Message Control
Time estimate: 15 minutes Please go through all the points in the following checklist. If necessary, confirm with IT Department any information you cannot verify before contacting your local COPA-DATA Representative. Screenshot and followed ...