Driver BuR41xx32: connection lose occur after some hours runtime

Driver BuR41xx32: connection lose occur after some hours runtime

Summary

When the runtime runs for a longer time (some hours) the connection is lost.

The diagnoseviewer logs following message: CBuR41xxObj::ParseString: Wrong Sequence Number (expected, is)

Description

When the runtime runs for a longer time (some hours) the connection is lost.

The diagnoseviewer logs following message: CBuR41xxObj::ParseString: Wrong Sequence Number (expected, is)

Solution

sequence number increasing is now limited to a value 65535



Issue Number: 29001
Fixed on Date: 4.3.2013
Versions: 7.00 0 BUILD 8