DNP332 driver sequence of events is not correctly considered

DNP332 driver sequence of events is not correctly considered

Summary

If multiple values are received by the DNP332 from an outstation with the same value but different timestamps or status, only the last received value is sent to the runtime.

Description

If multiple values are received by the DNP332 from an outstation with the same value but different timestamps or status, only the last received value is sent to the runtime.

Solution

An issue has been addressed in the DNP332 driver where values from sequence of events were not properly processed, and not all values were sent to the runtime by the driver. Now all values received with an external timestamp / statusflags are passed on to the runtime, also when the current value is the same.

Information

addressed with version 3900, available from version 7.00 SP0 build 1



Issue Number: 27066
Fixed on Date: 18.6.2012
Versions: 7.00 0 BUILD 1