DNP332 driver sequence of events is not correctly considered
Summary
If multiple values are received by the DNP332 from an outstation with the same value but different timestamps or status, only the last received value is sent to the runtime.
Description
If multiple values are received by the DNP332 from an outstation with the same value but different timestamps or status, only the last received value is sent to the runtime.
Solution
An issue has been addressed in the DNP332 driver where values from sequence of events were not properly processed, and not all values were sent to the runtime by the driver. Now all values received with an external timestamp / statusflags are passed on to the runtime, also when the current value is the same.
Information
addressed with version 3900, available from version 7.00 SP0 build 1
Issue Number: 27066
Fixed on Date: 18.6.2012
Versions: 7.00 0 BUILD 1
Related Articles
linear value adjustment confgured at the variable is not correctly considered in RGM
Summary When a linear value adjustment is configured at a variable, this is not correctly considered in all circumstances in the Recipe Groups Manager. At reading and writing shadow variables and recipes, the adjusted range is not considered, and a ...
Variables of the Math32 driver are not considered in the network rating
Summary When using variables of the Math32 driver in the rating calculation of the rated network, the values of these variables are not considered. DescriptionWhen using variables of the Math32 driver in the rating calculation of the rated network, ...
Checklist: Driver(s) cannot establish a reliable communication
Time estimate: 60 minutes Please go through all the points in the following checklist. If necessary, confirm with IT Department any information you cannot verify before contacting your local COPA-DATA Representative. Checklist usage: #. [Quick hints] ...
3S_V3 Driver : The length of WSTRING variables is not considered during variable Import.
Summary The length of a WSTRING variable is available in the Symbol file. During variable Online or Offline Import, the length is not considered and the WSTRING variable acquires the Default length "5" in zenon. The length of STRING variables is set ...
The DNP3_TG driver does not interrupt writing when the outstation response contains IIN 1.1, IIN 1.2 or IIN1.3 indicating that events are available.
Summary When writing a larger number of binary outputs, analog outputs or octet strings in sequence, for example through the Recipegroup Manager, the DNP3_TG master driver does not interrupt the writing when the outstation response contains IIN 1.1, ...