If multiple values are received by the DNP332 from an outstation with the same value but different timestamps or status, only the last received value is sent to the runtime.
If multiple values are received by the DNP332 from an outstation with the same value but different timestamps or status, only the last received value is sent to the runtime.
An issue has been addressed in the DNP332 driver where values from sequence of events were not properly processed, and not all values were sent to the runtime by the driver. Now all values received with an external timestamp / statusflags are passed on to the runtime, also when the current value is the same.
addressed with version 3900, available from version 7.00 SP0 build 1