Debug over CAN with GridConnect2 does not work for CAN2B

Debug over CAN with GridConnect2 does not work for CAN2B

Description

The CAN bus showed a remote frame with ID different from the extended-address set in communication settings because zenon did not apply the configured extended address when forming the CAN identifier.

The issue has been addressed and the behavior is now as expected. 

 

To benefit from this fix:

  • Update your zenon Software Platform to the latest build of zenon 16 or higher.


Item ID: 321806
Version: 16.00 Build: 679049