Creating new metering points with automatic value calculation is not possible. The output window displays the error "zenon logic project can´t be opened"

Creating new metering points with automatic value calculation is not possible. The output window displays the error "zenon logic project can´t be opened"

Summary

With the released version of zenon 7.50, in the 64bit editor, it is not possible to create new metering points with automatic value calculation. Instead, an error message is displayed, saying that the zenon logic project can´t be opened. 

Description

With the released version of zenon 7.50, in the 64bit editor, it is not possible to create new metering points with automatic value calculation. Instead, an error message is displayed, saying that the zenon logic project can´t be opened. 

Solution

For the automatic value calculation in metering points a zenon logic program has to be created in the background. In the 64bit version of zenon 7.50 there is a dll missing which makes it impossible for the metering point administration to create this program. By adding the missing dll file (k5prp.dll) the issue was fixed.

Issue Number: 36255
Fixed on Date: 12.4.2016
Versions: 7.50 0 BUILD 27465