Compatible runtime files use the original size of graphics inside symbols from a global project.
Summary
Symbols from the global project use the original size of graphics if the runtime files are created for an older zenon version. This can lead to distorted portrayal of the symbols.
Description
Symbols from the global project use the original size of graphics if the runtime files are created for an older zenon version. This can lead to distorted portrayal of the symbols.
Solution
The issue has been resolved and the correct project and version branches are used now.
Information
Workaround:
Export the symbol library from the global project into the project library gives a set of symbols which can be compiled for older zenon versions.
The Set of Screens can be modified after an XML-Export. (delete (g)).
if (g) is not unique as a prefix for symbols from a global project within a screen it might create new issues
Issue Number: 38745
Fixed on Date: 11.9.2017
Versions: 7.60 0 BUILD 40751