Command Processing: no interlocking text when action fails at second stage, while at first stage there was no interlocking yet.

Command Processing: no interlocking text when action fails at second stage, while at first stage there was no interlocking yet.

Summary

Command Processing, two-stage action 'command': issue when at first stage (i.e. Select) the interlocking condition is OK, but at second stage (Execute) - not anymore. Then when user press button to execute - the action cancels automatically and not informing the user. If at the first stage there was already the Select sent to PLC then the action sends to PLC correctly the Cancel. In 7.11 was OK - the user was informed.

Description

Command Processing, two-stage action 'command': issue when at first stage (i.e. Select) the interlocking condition is OK, but at second stage (Execute) - not anymore. Then when user press button to execute - the action cancels automatically and not informing the user. If at the first stage there was already the Select sent to PLC then the action sends to PLC correctly the Cancel. In 7.11 was OK - the user was informed.

Solution

Now a violated interlocking condition is also shown if this happens on execute stage.

Issue Number: 35883
Fixed on Date: 22.9.2016
Versions: 7.20 0 BUILD 31669 | 7.50 0 BUILD 31997