Array elements that are used in the zenon logic runtime and are linked to fieldbus configuration have a random value on startup
Summary
Under specific circumstances for array elements that are used in the fieldbus configuration, the initial value in the zenon logic runtime is not correctly updated on startup of the zenon logic runtime. Until the time when the array variable receives a value from the fieldbus driver the value is random instead of the initialization value "0" from the fieldbus driver.
Description
Under specific circumstances for array elements that are used in the fieldbus configuration, the initial value in the zenon logic runtime is not correctly updated on startup of the zenon logic runtime. Until the time when the array variable receives a value from the fieldbus driver the value is random instead of the initialization value "0" from the fieldbus driver.
Solution
An issue has been addressed in the zenon logic runtime where the initial value of an array element was not correctly taken over from the fieldbus driver.
Information
Issue Number: 34136
Fixed on Date: 7.4.2015
Versions: 7.50 0 BUILD 25796
Related Articles
Checklist: The Logic Service to Service Engine connection does not work
Time estimate: 30 minutes Please go through all the points in the following checklist. If necessary, confirm with IT Department any information you cannot verify before contacting your local COPA-DATA Representative. Screenshot and followed ...
Redundant License Configuration
Starting from zenon version 8.00 it is possible to share each license over the CodeMeter network. This allows you to have a dedicated license server. The license server can be any PC or virtual machine which runs CodeMeter. One license for two ...
zenon Changesets CSV
Here, you can access a comprehensive list of changes across all maintained versions of the zenon Software Platform as Excel Worksheets. This includes both implemented bug-fixes and new features. Additionally, these lists are available in as Excel ...
zenon Changesets Excel
Here, you can access a comprehensive list of changes across all maintained versions of the zenon Software Platform as Excel Worksheets. This includes both implemented bug-fixes and new features. Additionally, these lists are available in CSV format ...
logic to scada connection gets blocked if the variable from zenon side updates the value in shorter periode as the zenon logic cycle.
Summary 'Logic to SCADA Connection', the shared Memory used for this Connection, gets blocked if the variable from zenon side updates the value in shorter periode as the zenon logic cycle. Description'Logic to SCADA Connection', the shared Memory ...