Database error 0x80040154: Class not registered.

Database error 0x80040154: Class not registered.

Issue:
Archive can not be evacuated

Log shows error:
Database error 0x80040154: Class not registered.

Problem:
Engineering Studio configured a SQL provider to be used, which does not exist on the Service Engine PC.

Solution:
Install the configured SQL provider on the Service Engine PC.
    • Related Articles

    • FAQ: Historian configuration general recommendations

      1. Recommendation on hardware: Storage Memory CPU - High-speed SSD (Solid-State Drive). - Disk space capacity as detailed in the attached Excel sheet outputs. - RAM required to load the archive data is about 4 times greater the size of the respective ...
    • Archive configuration for best SQL evacuation performance

      The time required to evacuate data to a database increases linearly with the number of insert SQL statements. In earlier zenon versions, recorded values were evacuated to the target database sequentially using single-insert statements. From zenon 11 ...
    • Historian: SQL evacuation fails with certain archive files

      Description An error occurs in the Historian during the SQL evacuation of archive data. The evacuation fails for certain archive files. This occurs when the last value of a variable is "NaN". In this case, this value is expected to be skipped and ...
    • FAQ: What SQL server interfaces are offered by zenon?

      The most common ones are: The zenon Historian The Extended Trend The zenon Report Generator The zenon Report Engine The zenon SQL export functions The zenon SQL Driver and The zenon Process Gateway SQL module All these modules depend on an ODBC / ...
    • Database cannot be opened! (SQL Authentication Error)

      When opening zenon, one may encounter the following message in the output window: Taking a glimpse at the logs reveals that there are authentication errors regarding zenon's default database user "zenOnSrv". Therefore, no projects can be opened. ...