Alarm Status column does not correctly display active alarms when the setting "Use Reactivated Time" is used in project under specific circumstances
Summary
The Alarm Status is not correctly displayed as "active" under specific circumstances when the option "Use Reactivated Time" is used in the project. If an alarm for a variable becomes acive, than clears (without acknowledging the alarm) and then the alarm becomes active again, the Alarm Status column of the alarm list does not show the alarm as active.
Description
The Alarm Status is not correctly displayed as "active" under specific circumstances when the option "Use Reactivated Time" is used in the project. If an alarm for a variable becomes acive, than clears (without acknowledging the alarm) and then the alarm becomes active again, the Alarm Status column of the alarm list does not show the alarm as active.
Solution
An issue was addressed in the runtime where reactivated alarms were not treated as active alarms. Now the alarm status column correctly displays the active status of the alarm when the option "use reactivated time" is used in the project
Issue Number: 29300
Fixed on Date: 8.4.2013
Versions: 6.51 0 BUILD 21 | 7.10 0 BUILD 6571