AddIn: ScreenClosingEvent in combination with faceplates lead to service engine crash

AddIn: ScreenClosingEvent in combination with faceplates lead to service engine crash

Description

When closing a screen of the Faceplate type via the Add-In, the Service Engine is terminated. This happens due to incorrect sequence of events when closing. Now the "closed" event is triggered first for the screens contained in the container, and then for the faceplate image itself.
To fix this issue:
  • Update to the latest build of zenon 10 or 11.


Item ID: 253166
Version: 10.00 Build: 100998
    • Related Articles

    • FAQ: How can I backup the Service Engine data, the data created during Service Engine?

      The path of the Service Engine folder can be amended in the project properties and it is set into zenon6.ini (VBF30=) when the start project is set in Engineering Studio or in zenon Startup Tool. In the Service Engine folder, there is the subfolder ...
    • Using AddIn in combination with WVS

      Can AddIns be used in WVS? Simple answer: yes, but... Types of AddIns, Types of WVS There need to be distinguished between a AddIn Service and an AddIn Wizard. Whereas the first is started and stopped and reacts in between on events is the latter ...
    • AddIn does not start

      Check the Logs in DiagViewer. If it shows an ERROR in the GENERAL module which shows the exception: Scada.Internal.DotNetAddInExtension.AddInIntegration.Startup Cannot startup Add-In .NET Extension for instance id 'e1d3....'. Exception ...
    • Checklist: Data Missing in Service Engine

      Time estimate: 60 minutes Please go through all the points in the following checklist. If necessary, confirm with IT Department any information you cannot verify before contacting your local COPA-DATA Representative. Checklist usage: #. [Quick hints] ...
    • Checklist: The Logic Service to Service Engine connection does not work

      Time estimate:   30 minutes Please go through all the points in the following checklist. If necessary, confirm with IT Department any information you cannot verify before contacting your local COPA-DATA Representative. Screenshot and followed ...