The AccessOPCUA server no longer sends duplicate MonitoredItemNotifications in one responce.
The zenon OPC UA Process Gateway generates duplicate notifications for Monitored Items for a single value change of a variable.
This happens if the size of the queue for Monitored Items notifications is configured larger than 1 for the connected OPC UA clients.
This behavior has been corrected. >
To get the correct number of notifications again:
- Update to the latest build of zenon 8.10, 8.20, 10 or 11.