The selection of intervals for periodic transmission has been extended. The intervals apply to measured values that are not configured for spontaneous (COT=3), but for periodic transmission (COT=1). Configuration is done in the Sector configuration and in the configuration of the Information object settings.
The new Time for Periodic Transfer Interval 2 option has been added to the Sector Settings configuration dialog for this purpose. The existing Time for Periodic Transfer option has been renamed to Periodic Transfer Interval 1.
In the Information object settings configuration dialog, the existing Periodic Data Transfer option has been adapted and extended accordingly.