A specific IEC 60870 master timed out while waiting for the GI activation confirmation and interrupted communication with the AccessIEC870Sl Process Gateway when a large number of variables were used in one sector.
The issue has been addressed and communication now also works as expected when using a large number of variables in one sector.
To benefit from this fix:
- Update your zenon Software Platform to the latest build of zenon 11 or higher.