AccessIEC870SL: Process Gateway IEC60870-5-101 slave (serial) cannot establish communication with the remote master as it uses always link address = 1 regardless the configuration
Description
Process Gateway IEC60870-5-101 slave cannot establish communication serially to
remote master in zenon version 10 and later.
Cause:
The gateway always responds to the link status
request of the remote master with link address 01, regardless of its configuration. Therefore,
the link request is always answered incorrectly if the correct answer is not 01.
This behavior has been modified. The IEC60870-5-101
slave now again responds correctly to the link status request with the
correct link address. The communication is established.
To benefit from this fix:
- Update your zenon Software Platform to the latest build of zenon 10 or
higher.
Item ID: 266031
Version: 12.00 Build: 159727
Version: 10.00 Build: 159736
Related Articles
Checklist: Process Gateway cannot establish a reliable communication
Time estimate: 45 minutes Please go through all the points in the following checklist. If necessary, confirm with IT Department any information you cannot verify before contacting your local COPA-DATA Representative. Checklist usage: #. [Quick hints] ...
Checklist: Driver(s) cannot establish a reliable communication
Time estimate: 60 minutes Please go through all the points in the following checklist. If necessary, confirm with IT Department any information you cannot verify before contacting your local COPA-DATA Representative. Checklist usage: #. [Quick hints] ...
Checklist: Smart Client cannot establish a reliable communication
Time estimate: 60 minutes Please go through all the items in the following checklist. If necessary, confirm any information you cannot verify with the IT department before contacting your local COPA-DATA representative. Checklist usage: #. [Quick ...
Checklist: Process Gateway cannot start
Time estimate: 30 minutes Please go through all the points in the following checklist. If necessary, confirm with IT Department any information you cannot verify before contacting your local COPA-DATA Representative. Checklist usage: #. [Quick hints] ...
FAQ: How can I monitor and react on the communication status of my devices with zenon?
Data quality is very important to the integrity of a HMI or SCADA system. As such, zenon has numerous ways to monitor the communication status of different devices within your automation environment. Here are some options that you can use in your ...