8.00 RT crash due to DiagViewer message level DeepDebug of Connections module with string variable lenght above 330 chars

8.00 RT crash due to DiagViewer message level DeepDebug of Connections module with string variable lenght above 330 chars

Summary

Runtime crashes when a diagnostic logging with a very long string is created

Description

Runtime crashes when a diagnostic logging with a very long string is created

Information

In our tests we discovered that the lenght limit should be around 320 / 340 chars.

In case of projects with string variables longer than this limit , the user has to avoid enabling deebdepug on the zenRt32 Connection module



Issue Number: 211199
Fixed on Date: 27.2.2020
Versions: 8.00 0 BUILD 64633
    • Related Articles

    • Checklist: Process closes unexpectedly (***Non-reproducible***)

      Time estimate: 45 minutes Please go through all the points in the following checklist. If necessary, confirm with IT Department any information you cannot verify before contacting your local COPA-DATA Representative. Checklist usage: #. [Quick hints] ...
    • Checklist: Process closes unexpectedly (***Reproducible***)

      Time estimate: 30 minutes Please go through all the points in the following checklist. If necessary, confirm with IT Department any information you cannot verify before contacting your local COPA-DATA Representative. Checklist usage: #. [Quick hints] ...
    • Checklist: Message Control

      Time estimate: 15 minutes Please go through all the points in the following checklist. If necessary, confirm with IT Department any information you cannot verify before contacting your local COPA-DATA Representative. Screenshot and followed ...
    • VASS driver creates 'deep debug' messages in diagviewer without configuration

      Summary Drivers write a DEEPDEBUG log message for every advised variable although DEEPDEBUG log level isn't active Description Drivers write a DEEPDEBUG log message for every advised variable although DEEPDEBUG log level isn't active Information no ...
    • Variable name linked in action in command group cannot exceed 100 chars

      Summary When in command group an action has command variable name longer as 100 chars the compiler in Editor hangs or even crashes. In zenon, in general a variable name can be 128 chars long. Description When in command group an action has command ...